Executive standard: in accordance with GB/T8626-2007 "Test Method for Flammability of Building Materials"
Scope of application: The flammability testing machine for fireproof building materials products is mainly suitable for judging whether building materials have flammability test methods under specified conditions.
Technical Parameters:
1. The inner size of the combustion box: width 700× depth 400× height 810mm
2. Material: mirror stainless steel
3. The bottom is a natural vent, and the vent is composed of a square box.
4. Open area: 25×25mm, height: 50mm
5. Burner: The burner is composed of a nozzle with a hole diameter of ¢0.17mm and a regulating valve, and is equipped with four air suction holes of ¢4mm at an angle of 45°.
6. Flame height: 20±2mm, high-voltage electronic ignition, automatic ignition and reset
7. Gas: propane gas with purity of more than 95% (provided by the user)
8. Specimen clamp: composed of two U-shaped stainless steel frames, with a width of 15mm and a thickness of 5.0mm
9. Timer: 0~99.99S/M/H can be set
Key features:
1. The box of the test device is bent by stainless steel plate (δ1.5mm), which has the characteristics of beautiful appearance, corrosion resistance and anti-aging.
2. This instrument is designed and manufactured with all stainless steel materials, with six moving parts: (1) Y-direction movement (2) X-direction movement (3) Z-direction movement (4) Y-direction sliding (5) rotation around Z-axis (6) burner swing around X-direction -450~+450.
3. This instrument adopts a manual mode to realize the relative movement of X, Y and Z between the tested piece and the burner, as well as the quadruple rotation around the Z axis, which can easily determine the relative position between the tested piece and the burner, and realize various test methods specified in GB/T8626-2007.
4. The instrument is equipped with a positioning switch, plus a buzzer, which is convenient for the timing and end of the combustion test.
5. This instrument is equipped with a manual adjustable damper device, and the twist turns to the right to open the damper, and vice versa. When power ventilation is used, adjust the size of the damper to the air flow rate of 0.7+/_0.1 m/s and lock the lock nut.
When natural convection is used, the damper is opened to the maximum and locked.
At present, this machine is in stock, welcome customers and friends to order!